Single-phase
Transformers

TFM

Safety transformers with galvanic isolation provide a reliable supply to power circuits with the safety measures “protective separation” or “protection through shutdown”.
 Double or reinforced isolation between the primary and secondary sides protects SELV and PELV circuits. Safety transformers provide safety extra low voltages below 50 Vac or 120 Vdc.
Design:
Safety transformer according to
DIN EN 61558-2-6
Power Output: 100-10000VA
Input Voltage: Max. 1000 VAC
Output Voltage: MAX. 50 VAC
Frequency: 50/60 Hz
Ambient Temperature: 40 C
Protection Degree: IP00
Protection Class: I
Insulation Class: B (130 ° C) - standard up to 5 kVA, F (155 ° C) -standard above 5 kVA
3TF-350-103v22
TYP VA X1 X2 Y1 Y2 H Z1 Z2 KG
312**** 100 122 90 53 39 140 5 10 2,1
312**** 125 122 90 53 39 140 5 10 2,5
312**** 160 122 90 63 49 140 5 10 4,3
312**** 250 152 113 67 50 158 6 11 4,9
312**** 320 152 113 82 65 168 6 11 5,8
312**** 400 152 113 82 65 168 6 11 6
312**** 500 183 136 76 57 190 7 12 7,5
312**** 630 183 136 86 67 190 7 12 8,7
312**** 800 183 136 96 77 190 7 12 11,5
312**** 1000 183 136 96 77 190 7 12 14,6
312**** 1250 243 185 97 71 260 9 14 16
312**** 1600 243 185 107 81 260 9 14 20,5
312**** 2000 243 185 117 91 260 9 14 23
312**** 2500 305 224 124 94 320 10 15 27
312**** 3200 305 224 152 122 320 10 15 33
312**** 4000 305 224 152 122 320 10 15 34,5
312**** 5000 305 224 162 132 320 10 15 39
312**** 6300 370 264 162 132 380 10 15 52
312**** 8000 370 264 185 155 380 10 15 54
312**** 10000 430 316 205 173 440 12 17 62

All data are approximate, deviations may be possible. Other dimensions and technical changes are available on request.